Waterproofing in Morocco: flat roofs, membranes, sealants and the flood test

Flat-roof waterproofing is one of the few site trades in Morocco governed by a mandatory workmanship standard: NM 10.8.913, the Moroccan counterpart of the French roofing code for flat and pitched roofs with waterproofing. Several products are also of mandatory application, including synthetic roofing sheets (NM EN 13956), damp-proof sheets, rubber waterstops and joint sealants (NM ISO 11600). When insulation is added to a roof, the energy regulation RTCM (Decree No. 2-13-874) applies too. On site, the decisive proof is a successful flood test before the protection layer goes down.

Scope

This page concerns roof terraces (accessible or not), balconies and loggias over habitable rooms, wet-room floors where the CPS calls for tanking, basement walls and the damp-proof course at the base of walls. It includes the falls, upstands, outlets, expansion joints and sealant joints that make a waterproofing system complete.

It opens when the architect's details are drawn and the supporting slab or screed has been accepted, and closes when the roof has passed its flood test and been protected; the follow-up continues through the ten-year liability period, during which any leak threatening the building must be reported.

Regulatory table

Reference, edition, status, the text that makes the rule mandatory and the verified source (standards catalogue 2026-10-25; NM statuses checked against the official list of the Ministry of Industry and Trade).

ReferenceEditionStatusText making it mandatorySourceNote
NM 10.8.913
Travaux de bâtiment — étanchéité des toitures-terrasses et toitures inclinées avec éléments porteurs en maçonnerie
NM 10.8.913-2020mandatoryDécision/arrêté d'homologation n° 2344-20MCINET listMandatory workmanship standard for waterproofing flat and pitched roofs; the reference for supports, upstands and outlets.
NM EN 13956
Feuilles d'étanchéité de toiture plastiques et élastomères
NM EN 13956:2016mandatoryDécision/arrêté d'homologation n° 2674-16MCINET listPlastic and elastomeric roofing sheets; mandatory product standard.
NM EN 13969 / 13970 / 13967 / 14909 / 14967
Feuilles souples d'étanchéité (remontées d'humidité, pare-vapeur, barrières capillaires)
NM EN 13969:2020 ; NM EN 13970:2020 ; NM EN 13967:2020 ; NM EN 14909:2020 ; NM EN 14967:2020mandatoryDécision/arrêté d'homologation n° 3007-20MCINET listDamp-proof sheets, vapour barriers and capillary barriers; mandatory for basements and wall bases.
NM ISO 11600
Produits pour joints Classification et exigences pour les mastics ; (IC 10.8.748)
NM ISO 11600:2018mandatoryDécision/arrêté d'homologation n° 3946-18, entrée en vigueur le 15/08/2025MCINET listClassification of joint sealants; mandatory since 15/08/2025 under approval decision No. 3946-18.
NM 05.2.520
Bandes d’arrêt d’eau - Produits en caoutchouc – Spécifications
NM 05.2.520-2005mandatoryDécision/arrêté d'homologation n° 277-05MCINET listRubber waterstops at concrete joints of tanks and buried walls; mandatory.
NM 10.8.912
Plaques de bardeaux bitumes a armature en feutre cellulosique dites bardeaux bitumes cellulosiques Spécifications
NM 10.8.912-2010mandatoryDécision/arrêté d'homologation n° 1250-10MCINET listBitumen shingles on cellulose felt for pitched roofs; mandatory where this product is chosen.
NM EN 13707
Feuilles bitumineuses armées pour l'étanchéité de toiture
2016approved—IMANORReinforced bitumen sheets for roofing; homologated, to be quoted in the CPS for the usual bituminous systems.
Décret n° 2-13-874 du 15/10/2014
Règlement général de construction fixant les règles de performance énergétique des constructions (RTCM)
2014mandatoryThe text itself (published in the Official Bulletin)full textEnergy performance regulation: governs the insulation laid under or over the waterproofing on a roof terrace.

Materials and documents to request

MaterialStandardsSupporting documentsBasis
Reinforced bitumen membranesNM EN 13707Product designation and system description on the delivery note, matching the CPS; roll labels kept.Specification (CPS) requirement
Synthetic roofing sheets (PVC, TPO, EPDM)NM EN 13956Conformity with the mandatory standard stated by the manufacturer; installer trained for the system.Legal obligation
Joint sealants (expansion joints, perimeter joints)NM ISO 11600Class of sealant printed on the cartridge, suited to the joint type in the architect's detail.Legal obligation
Damp-proof course at wall baseNM EN 13969 / 13970 / 13967 / 14909 / 14967Data sheet of the sheet used and photo of its placement before the next course of masonry.Legal obligation

Who does what

PartyRole
ArchitectDraws the roof falls, upstand heights, outlets, overflows and joints, and witnesses the flood test.
Waterproofing contractorChecks the support before laying, installs the system to NM 10.8.913 and the manufacturer's instructions, and runs the flood test.
Structural contractorDelivers a clean, cured slab with the falls and upstands ready, and leaves outlets at the right place.
Structural engineering consultancy (BET)Checks that the roof can carry the protection layer, insulation and any planted or paved finish.
Client (owner)Keeps the test report and product evidence, and reports any leak promptly during the liability period.

Inspection milestones

  1. Architectural details and coordination of openings Good practice
    Roof plan with falls and outlets, upstand and threshold details, and joint layout drawn before the slab is cast.
  2. Basement and buried walls accepted Specification (CPS) requirement
    Basement tanking and damp-proof membranes inspected and photographed before the walls are backfilled.
  3. Roof waterproofing tested Specification (CPS) requirement
    Support accepted, membrane laid, upstands and outlets finished, flood test passed and recorded before protection.
  4. Ten-year liability: serious defects followed up Legal obligation
    Any leak that threatens the building reported at once and documented for the insurer during the liability period.

Common non-conformities and follow-up

FindingAction
Ponding on the roof after rain because the falls were not formed.Before waterproofing: rebuild the screed to falls. After: assess with the architect whether the system can tolerate it or must be redone.
Upstand too low under a door threshold or at the parapet.Raise the upstand or redesign the threshold with the architect before the flood test.
Flood test reveals a leak in the room below.Drain, locate and repair, then repeat the test; no protection layer is laid until a test passes.
Membrane laid on a damp or dusty slab.Strip the affected area, let the slab dry, clean and prime, then lay again.

Frequently asked questions

Is there a Moroccan standard for flat-roof waterproofing?

Yes. NM 10.8.913 sets the workmanship rules for roofs with waterproofing elements and is of mandatory application.

What is a flood test and is it required?

The roof is filled with water for a set period and the rooms below are watched for leaks. The CPS usually requires it; it is the only convincing proof before the roof is covered.

Are sealants regulated?

Yes. Joint sealants are classified under NM ISO 11600, which became mandatory in August 2025; the class must suit the joint.

Does roof insulation have to meet the RTCM?

When the roof is part of the heated or cooled envelope, the RTCM (Decree No. 2-13-874) sets its thermal performance by climate zone; the architect or thermal engineer justifies it.

Who is liable for a leaking roof after handover?

The contractor and designers, under the ten-year liability for defects that threaten the building's soundness, as provided by their contracts and the law. Report leaks quickly and keep the test report.

Sources, author and revisions

Written by , architect · under review · updated . Professional reading, separate from the text of the standard: each requirement is classed as a legal obligation, a specification (CPS) requirement or good practice.

Revision log

All standards for this trade (66)

In short: for the "Waterproofing" trade, the library lists 1 Moroccan regulation(s), 6 mandatory Moroccan standard(s), 14 approved NM and 7 foreign reference(s) used as equivalents.

Moroccan regulations (1)

Mandatory Moroccan standards (NM) (6)

Approved Moroccan standards (NM, voluntary) (14)

European and French standards (EN, NF, DTU) (4)

Other jurisdictions (equivalents) (3)

Cross-cutting texts (all trades) (38)

2026 reference prices — Waterproofing

Public reference prices from the CITURBAREA materials library (October 2026), in dirhams excluding VAT; 20% VAT on top (incl. VAT = excl. VAT × 1.2), Rabat-Salé-Kénitra base. These are benchmarks, not supplier prices.

MaterialFrom (excl. VAT)From (incl. VAT)Range excl. VATReliability
Bitume oxydé25 DH / kg30 DH / kg25 DH – 25 DHC (indicative)
Drain agricole / géodrain20,83 DH / ml25 DH / ml20,83 DH – 20,84 DHC (indicative)
Enduit hydrofuge de cuvelage27,63 DH / kg33,16 DH / kg27,63 DH – 28,47 DHC (indicative)
Mastic d'étanchéité (cartouche)49,16 DH / u58,99 DH / u49,16 DH – 78,97 DHC (indicative)
Membrane autoprotégée ardoisée 4 mm42,83 DH / m²51,4 DH / m²42,83 DH – 43,35 DHC (indicative)
Membrane bitumineuse 3 mm35 DH / m²42 DH / m²35 DH – 40,52 DHC (indicative)
Membrane bitumineuse SBS 4 mm36,66 DH / m²43,99 DH / m²36,66 DH – 40,95 DHC (indicative)
Primaire d'accrochage bitumineux (EIF, au kg)29,16 DH / kg34,99 DH / kg29,16 DH – 29,17 DHC (indicative)
Bande butyle alu Buty Band 100 mm × 10 m16,58 DH / ml19,9 DH / ml16,58 DH – 16,59 DHC (indicative)
Bande d'étanchéité Butyband / Alu Band 10 m × 10 cm13,33 DH / ml16 DH / ml13,33 DH – 13,34 DHC (indicative)

Detail in the estimator → · Reference prices and data sheets →

52 materials for this trade in the materials library. Étanchéité

Guides for this trade

See products, data sheets and supplier prices

Detailed offers by supplier, technical data sheets and product comparison are reserved for account holders. The account is free; no contact details are exchanged, everything goes through CITURBAREA.

Create my free account → Professional? Create my pro space

Estimate my project Book a call

Library maintained by CITURBAREA, construction and architecture platform in Morocco · tools for architects.

All trades

Site set-up · Earthworks · Foundations · Retaining walls & basement · Reinforced-concrete frame · Masonry · Thermal insulation · Renders & screeds · Façades · Aluminium exterior joinery · Interior wood joinery · Metalwork, railings · Suspended ceilings, plaster · Floor finishes · Wall finishes (tiles, zellige) · Painting · Plumbing & hot water · Sanitary fixtures · Electrical (power & low current) · HVAC · Lift · Fire safety · Solar thermal & PV · Site works & landscaping · Swimming pool

Does your project comply with these texts?

A registered architect checks your project's compliance, from building permit to handover. Free overall estimate, first call with no commitment.

Estimate my project → Book a free video call Create my free account

Stay informed

Material prices, new planning rules and site advice: one letter a month, written by an architect.

▶ Subscribe to the YouTube channel Channel of architect Yassine AT-TARASSI: sites, prices and procedures on video.
Create my free account →

General information based on official texts: it does not replace a review of your own file. — , architect · Arc Bati Architecture